Consists of control module (panel mountable) and separate probe unit. Two probes can be used with one control module to provide sequence filling/emptying over given distance. Choice of high level control (RLM48/T) or low level control (RLM48/LT). Adjustable time delay prevents spurious operation from liquid splashing. |
Supply |
110/230V ac |
Load | 1.5A max, 50 mA dc |
Ambient Temp. | -15°C to +45°C for control module |
Output | SPCO relay rated @ 2.5A 240V ac non-inductive |
Output Mode | RLM48/T - normally ON (high level) RLM48/LT - normally OFF (low level) |
Calibration | Analogue rotary over range of 500 ohms to 30K ohms |
Indicators | Output LED |
Mounting | 11 pin relay base for RLM modules |
Protection | IP40 for RLM modules, IP65 typically for probes |
Code/Weight | RLM48/T, RLM48/LT - 220g RLP1 - 600g + probe rod MRP2 - 300g |