Capacitance level control system, consists of 3 parts: Control unit DRC105(A), signal Transverter DCT2, probe head/probe. Type depends upon application/temperature. RPP1(polyproylene) upto 125°C, RPK1 (PEEK) upto 250°C. LED display shows calibration & run mode readings. Power shield compensator, prevents false signalling due to material build-up on probe rod. The DMR2 is ideal for all level control application where vibration and/or temperature prevent the use of a fully self contained controller. |
Supply | 110/230V ac, 24V dc |
Load | 1.5A max, 50 mA dc |
Ambient Temp. | -10°C to +50°C for DRC105(A). Probe head depends upon type used (upto 250°C) |
Probe Heads | RPP1: Polypropylene suitable upto 125° RPK1:PEEK suitable upto 250°C.......... |
Output | SPCO relay rated @ 2.5A 240V ac non-inductive |
Output Mode | Switch selectable for normally ON (high level), or normall off (low level) |
Calibration | Membrane pushbuttons with LED display. Automatic calibration with full manual override |
Indicators | Digital display for calibration and run mode settings, plus power, timer and output LED's |
Mounting | 1" BSP for RPP1/RPK1, DIN rail for DRC105(A) |
Protection | DRC105(A) - IP40, IP65 - all other parts |
Compensator | Power shield compensates for material build up between probe and vessel wall (earth/ground). Prevents false signalling. Ideal for sticky or viscous materials |
Code/Weight | DRC105(A) - 275g DCT2 - 120g RPK1/RPP1 - 410g plus probe rod. |
Approval | ATEX 1D Ex td A20 (Ex iaD) 20 T125°C (Request Certificate for full details). |