A DIN standard limit switch packaged underspeed monitor with relay output. Output given if input speed reduces by 20% or more by customer programmed speed setting. Programmable start-up delay, allows machinery to achieve normal running speed. ATEX approved. |
Supply |
12-240V dc/ 24-240V ac |
Output | SPCO relay 3A 240V max. non-inductive. |
Output State | Output energised (ON) at set running speed, de-energises if rotation falls by 20% or more below set speed. |
Operating range | 12mm |
Calibration | Start-up delay & set running speed user programmable using magnet (supplied) applied to a target area on body of sensor. Automatically calibrates for 20% under normal running speed. |
Start-up delay | Programmable start-up delay. Output energises for time period irrespective of incoming pulse signal, allows machinery to achieve running speed. Max. 30 second delay. |
Hysterisis | 15% of operating range |
Ambient temp. | -15°C to +50°C |
IP Rating | IP65 |
No. of Cores | 5 |
Weight | 500g |